Friday 11 May 2012

Boiler water tests


Boiler water tests
Add caption

Corrosion and tube failure caused by water chemistry

Recommended ranges( Co-ordinated phosphate treatment for w/t boiler )

pH- 9.6 to 10.3
PO4 - 4 to 20 ppm
N2H4 - 0.01 to 0.03 ppm
TDS - < 150 ppm
Cond pH - 8.6 to 9.0
Cl - 20 ppm
O2 - 10 ppb
Si - 10 ppb

Chlorides
    • Measure 100ml of sample water into a casserole
    • Add 10 drops phenol pthalein (RE 106)
    • Neutralize with sulphuric acid
    • Add 10 drops of Potassium Chromate
    • Titrate Silver Nitrate untill sample just turns brick red
    • ppm as CaCO3= (ml x 10) ppm
TDS
    • Measure 100ml of sample water into a casserole
    • Add 10 drops of phenolpthalein
    • Neutralise with TDS reagent (acetic acid)
    • Temperature compensate then read off scale in ppm.
Phosphates
    • Fill one 10 ml tube with distilled water
    • Fill one 10 ml tube with boiler water tests.
    • Add 0.5 ml sulphuric acid (RE 131) to each
      Add 0.5 ml Ammonium Molybdnate (RE130) to each
      Add 0.5 ml Aminonapthol Sulfonic acid (RE 132) to each
      Stir well between each addition
    • Wait 3 minutes for calorimetric compaison Alternately Vanado-molybdnate test
    • Place 5 ml boiler water in 10 ml tube
    • Place 5 ml distilled water in other 10 ml tube
    • Top both to 10 ml with Vanado-molybdnate reagent
    • Place in colour comparator and compare after 5 mins
Hydrazine
    • Add 9ml distilled water to one tube
    • Add 9 ml boiler test water to anouther
    • Add 1 ml hydrazine reagent to each
    • Use colour comparator
Alkalinity Phenolpthalein
    • 100 ml filtered water
    • Add 1 ml phenolpthalein
    • If pH >8.4 Solution turns pink
    • Add H2SO4 untill pink disapears
    • Ml 0.02N H2SO4 x 10 = ALk in CaCO3 ppm
    • Measures hydroxides and carbonates in sample, bi-carbonates do not show up so sample should not be allowed to be exposed to the air for too long
Alkalinity Methyl orange
      Bi carbonates do not show up in the phenolpthalein sample as they have a pH < 8.4. Bi carbonates can not occur in boiler but if suspected in raw feed then the following test.
    • Take phenolpthalein sample, add 1 ml methyl orange
    • If yellow, bi carbonates are present
    • Add H2SO4 untill red
    • Total 0.02N H2SO4 x 10 = Total Alk in CaCO3
pH
    • 100 ml unfiltered sealed water poured into two 50 ml glass stoppered test tubes
    • Add 0.2 ml pH indicator to one ( pH indicator vary's according to required measuring range)
    • Use colour comparator
    • Due to difficulty of excluding air, electronic pH meter preferred
Sulphite reserve
    • Exclude air at all stages
    • 100 ml unfiltered water
    • Add 4 ml H2SO4 + 1 ml starch
    • Add potassium iodate-iodide untill blue colour
    • ml Iodate-Iodide sol x 806 / ml of sample = SO3 reserve in ppm
Ammonia in feed
    • Only necessary where N2H4 used in blr
    • Pour condensate sample into two 50 ml colour comparator tubes
    • Add 2 ml Nessler reagent to one
    • Wait 10 mins
    • Use colour comparator

2 comments:

  1. Hello, thank you for sharing such a informative blog. I Was working in water testing service form very long time they were tested water from one of the best water testing company in India.Their are many water testing company but make sure you choose best and good experienced only. Keep sharing

    ReplyDelete
  2. Thanks for sharing nice information with us. I like your post and all you share with us is up to date and quite informative, I would like to bookmark the page so I can come here again to read you, as you have done a wonderful job. asbestos air testing

    ReplyDelete