Showing posts with label Generators. Show all posts
Showing posts with label Generators. Show all posts

Friday, 22 June 2012

AC switchboards

AC switchboards
AC switchboards
If voltages exceed 250 volts d.c. or 55 volts A.C. then the switchboard must be dead front (no exposed live parts at the front) of the metal clad type.

Bus bars

High conductivity copper rated to withstand the thermal and electromagnetic forces which would arise in the event of a short circuit at the bus bars with all the generators in parallel. The bus bars will withstand these conditions for the length of time it takes for the alternator circuit breakers to trip or back up fuse to blow. Certain instruments and controls require a feed direct from the bus bars. Any connection between the bus bars and protecting fuses must be capable of withstanding maximum fault level. Standard practice is to provide a three phase set of fuses, known as 'Back Up' fuses, as near to the bus bars as possible. Connections are then led to the racks of the many instruments fuses fitted.

Circuit breakers

Must be capable of making and breaking under normal conditions and also abnormal conditions such as a short circuit. As the circuit breaker must be able to withstand closing onto a fault conditions without sustaining damage, it is of heavy construction. Fitted with an over current release and overloads with time lags, a circuit breaker can be used as follows;
  1. To control the output of a generator
  2. As a direct on line starter
  3. Control outgoing feeder circuits
On modern switchboards 'draw out' circuit breakers may be fitted. In the open position the whole circuit breaker can be wound clear of the bus bars, thus full inspection and maintenance can be achieved without the necessity of de-energising the bus bars so providing a separate isolating switch. The 'plug in' contacts joining the circuit breaker to the bus bars are not capable of taking the breaking load and it is essential that the circuit breaker is in the open position before any attempt is made to withdraw it. A mechanical interlock is fitted arranged to trip the circuit breaker before the winding handle can be inserted,
The breaker also has a mid position, in this position the control circuits are still connected with the bus bar connection isolated. The electrical operation of the breaker can then be tested.
Circuit breakers are normally fitted with under voltage protection and tripping is accomplished by shorting or open circuiting the no-volt coil which releases the latching in mechanism. The no-volt coil may also be open circuited by a reverse power relay and an overload trip fitted with a time delay

Instruments


    The following instruments are the minimum that must be fitted;
    • Bus bar voltmeter and frequency meter
    • Volt meter and frequency meter, with selector switch to measure incoming machine conditions
    • Ammeter with phase selector switch for each alternator
    • Watt meter for each alternator
    • Synchroscope and if check synchroscope not fitted lamps
    • Earth leakage indicator
    Additional instruments that may be fitted
    • Watt hour meter
    • Power factor meter
    • Alternator excitation ammeter
    • Alternator excitation volt meter
    • kVAr meter
    • Share connection supply meter
    • Emergency batteries on discharge meter
When a check synchroniser is fitted it is there to prevent connecting an incoming machine to the bus bars whilst out of phase, it is not there as aid to synchronising. In an emergency the 'in synch' light may be used to indicate when the breaker may be closed. When an incoming machine is selected, its no-volt coil and circuit breaker contactor relay coil are connected in series with contacts on the check synchroniser. These contacts must be closed, that is the machine in phase with the bus bars, before the breaker contactor relay may be energised. If starting from a dead ship the check synchroniser must be switched to off before the first generator is put on the board.

Protection


  1. Overload protection-fitted to circuit breakers
  2. Reverse power-When motive power is removed an alternator will try to become a synchronous motor and draw current from the circuit. A reverse power relay will operate after about 2 seconds and about 2-3% reverse power for turbines, 10-12% reverse power for diesels. The time delay prevents tripping during paralleling and taking the alternator off the board.
  3. Preference trip-automatically , and sometimes sequentially, sheds load from board to maintain supply to essential services during periods of overload.
  4. Fuses-Usually of the HRC type
  5. Discrimination-The protective device closest to the fault should operate and protect other services
  6. Group starter board-Large demand sections may be separated from the main switchboard by fuses and circuit breakers.

Automatic voltage regulators

Shall be supplied separately from all other instrument circuits. Protection should be by fuses mounted as close to the supply connections as possible.

Shore supply connections

  1. Where arrangements are made for the supply of electricity from a source on shore or other location a suitable connection box has to be installed in a position in the ship suitable for the convenient reception of flexible cables, it should contain a circuit breaker or isolating switch, fuses, and terminals of adequate size to receive the cable ends.
  2. For three phase shore supplies with earthed neutral terminals are to be provided for connecting hull to shore earth
  3. An indicator for shore side connection energised is to be provided.
  4. A means for checking polarity or phase rotation is to be provided
  5. At the connection box a notice indicating ships requirements with respect to supply as well as connection procedure.
  6. Alternative arrangements may be submitted for consideration.

Limiting voltage

Limiting voltage dip and response time under impact loading

The effect of a large load suddenly switched on to a small power installation such as a ships plant will be an instantaneous dip in the generator voltage. This effect, due to the transient reactance on starting, cannot be obviated either in a self regulated machine, or in a conventional generator with A.V.R.
The sluggish response of the excitation systems limits the speed of voltage recovery.
In a self excited generator the dip is less and the recovery time greatly improved. (say 0.3s against 0.7s)
In order to maintain constant voltage, under varying conditions, excitation must be varied.
Variation of voltage at constant excitation
graph showing variation in voltage with different power factors
Variation of excitation at constant voltage
graph showing variation in voltage with different excitation

Parallel operation of generators


D.C. generators

For compound wound D.C. generators it is usually sufficient to ensure that the voltages of the incoming generator is the same as the bus bar voltage. The equalising connection joining the junctions between the armatures and their series fields is incorporated in the circuit breaker in such a way that the equalising connection is automatically closed before and opens after, the main contacts. By adjustment of the shunt field regulator the load sharing may be controlled

A.C. alternators

    To parallel alternators the following conditions are required;
    1. Same voltage-checked with the voltmeter
    2. Same frequency-checked with the frequency meter and synchroscope
    3. Same phase angle-checked with synchroscope
    4. Same phase rotation-checked with rotation meter. Only important when connecting shore supply, or after maintenance on switchgear or alternator.

Load Sharing Of Alternators In Parallel

Alternators in parallel must always run at the same speed. After a machine has been paralleled and is required to take up its share of the load, this will not be achieved by adjusting the field excitation current. Although the increase in e.m.f. will cause a current to flow in the busbars, and this will show on the machines ammeters, this is a reactive current that lags the e.m.f. by 90o and produces a reactive (kVAr) but not kW. Its only effect is to alter the operating power factor of the alternator. More power may be obtained at the bus bars from the incoming alternator only by supplying more power to its prime mover. This increase of steam or fuel supply is achieved by altering the governor setting either electrically or manually.
After adjusting the governor the incoming machine takes up its desired amount of the kW loading and this is recorded on the machines watt meter. However, if the kW loading is shared equally between two machines it may be found that the Load Current of the incoming machine is more or less than the other machine. This is fue to the incoming machine having a different power factor. This may be corrected by adjusting the excitation of the incoming alternator.

    Thus after paralleling an alternator;
    1. Adjust prime mover governor until kW loading is correct
    2. Adjust field excitation current until current sharing is correct.
If the alternators have similar load characteristics, once adjusted, the load will continue to be shared. If the load characteristics of alternators vary, the kW loading and load current sharing may require readjusting under different load conditions.

Load sharing of alternators

No1 on load No1 on load
No1 on load, No2 synchronised and taking 100kW
No1 on load, No2 taking 100 kW
No1 and No2 sharing load after adjusting governor settings, excitation adjusted to prevent excessive volt drop in No2
No1 , No2 sharing load
No1 and No2 sharing load with balanced power factors by adjusting excitation
No1 , No2 sharing load with balanced power factors

The effects of altering Torque and Excitation on single phase alternator plant-and by extrapolation a 3-phase circuit

Schematic showing two alternators attached to bus bars
Before paralleling, by varying Rb, adjust the excitation current in the rotor field of 'B' until Va=Vb. When in phase and at the same frequency synchronising may take place.
If there was no external load on the bus bars the torque on the prime movers of A and B is only that required by its own alternator and Ra and Rb are adjusted so that Ea and Eb are equal.
Vector diagram for two alternators in parallel
Relative to the bus bars Ea and Eb are acting in the same direction with each other making the top bar positive with respect to the bottom bar.

Varying the driving torque

Vector diagram for two alternators in parallel, one lagging
If the driving torque of 'B' is reduced (less fuel supplied) the rotor falls back by an angle say p.f.(b) giving a resultant e.m.f. of Ez in the closed circuit.
The e.m.f. Ez circulates a current I which lags behind Ez by angle p.f.(a).
This circulating current Iis more or less in phase with Ea and in opposition to Eb.
This means that A is generating power to motor B and this will compensate for any loss of power in the prime mover of B.
Once the power increase in A equals the power loss of B balance is restored and A and B continue to run in synchronism.
Therefore the power is shared by adjusting the torque ( fuel input.)
Slight loss of power in B-is taken up by an increase in power from A. The terminal voltage will not vary and the speed and frequency will stay the same or drop only very slightly.
Large loss of power in B-with a large circulating current from A to B the alternator A will try to drive B as a synchronous motor. The amount of full load power required to drive an alternator as a motor is only 2 to 3% for a turbine and 10 to 12% for diesel engine.
As the circulating current flows from A to B the reverse power trip on B will operate after about 3 to 5 seconds.
All the load now falls on A which will probably cause the overload trip to operate and 'black out' .

Varying excitation

Vector diagram for two alternators in parallel, one reduced excitation Consider A and B are exerting the torque required by its alternator and the generated e.m.f. Ea and Eb are equal. There is no circulating current.
By reducing Rb the excitation current in the field of B can be increased and Eb will increase. Ez is the resultant difference (Eb - Ea) which will give a circulating current I through the synchronous impedances of the two alternators. As the machines are similar the impedance drop in each will be 1/2Ez so the terminal voltage
V1 = Eb - Н Ez = Ea + Н Ez
Therefore increasing the excitation current will increase the terminal voltage
As p.f.(a) is almost 90o the Power circulating from B to A is very small
Ez I Cos [ p.f.(a)] approx equals Zero (Cos 90o = Zero)

Effect of reducing Excitation

By increasing Rb the reduction of the field excitation current of B will reduce the terminal voltage Ea>Eb terminal Voltage V = Ea - Н Ez = Eb + Н Ez
The circulating current I from A to B will have a large 'Wattless' component. Machine A now has more of the lagging reactive current and its power factor is reduced. Too large a reduction in excitation current in B with subsequent increase in load current in A could cause the current overload trip of A to operate. This could be followed by the low voltage or the overload trip of B operating causing a black out.

Voltage regulation

 Graph showing effects on voltage of changing power factor The graph demonstrates that excitation must be increased (generally) with increasing load to maintain terminal voltage
 Graph showing change in terminal voltage worsens with reducing power factor
The worse the power factor the worse the terminal voltage change during load change.
Voltage regulation = DV when load removed/ Full load terminal voltage
At 1.0 p.f. = AC/ OA
At 0.8 p.f = AD/ OA
Therefore lower p.f. = greater voltage regualtion

Air Gap

If the air gap around a rotor is not uniform the motor may not start in certain positions. Because the rotor is not centred, probably due to worn bearings, there is an out of balance magnetic pull. Radial play in between the shaft and the housing should be detected by hand and bearing wear detected by feeler gauge between the rotor and the stator, or armature and field poles may be measured at three or four fairly equidistant points around the machine. If possible one measurement should be made at the bottom of the machine and another in line with the drive. Compare with previous records to check wear. At minimum air gap. Clearance of the bearings should be renewed to avoid the possibility of the rotor rubbing on the stator.
On small machines two feelers on opposite sides of the rotor should be used to avoid error caused by rotor movement from normal position when only one feeler gauge is used.
In synchronous motors and D.C. motors sparking may occur if the radial air gaps between the armature and the field poles are unequal. If necessary renew bearings or add or remove soft iron shims from under the pole shoes. Unequal field strength has a similar effect of sparking at the brushes. This might be due to short circuit or earth fault on the field coils, or a short circuit on the shunt and field coils.
An increase of air gap gives an increase in 'reluctance'.
In a salient pole A.C. generator this fact may be used to produce a sinusoidal flux density curve by gradually increasing the length if the air gap towards the pole tips.
profiled air gap voltage generated with profiled air gap In the induction motor the air gap should be as small as possible if the motor is to act with a high power factor. An increase in air gap increases the reactance of the motor and lowers its power factor. Small motors are accurately machined and centring of the rotor is very important so ball or roller bearings are fitted.

Air gap Motor size
0.25mm 1kW
0.75mm 10kW
2.0mm 100kW

Generators type

Generators
Generators type

The Alternator

The synchronous machine consists essentially of (a) a field system excited by direct current and (b) an armature. Almost invariably the armature is the stationary member and the field system the rotating member. The induced e.m.f. in the armature winding is a motionally induced e.m.f. and its mode of production identical with that of the D.C. machine. The only difference is that it is the magnetic field which moves whereas the armature conductor is stationary. As with a D.C. machine the e.m.f. induced in an individual armature coil ia an alternating e.m.f. and consequently by bringing the winding out to fixed terminals, the e.m.f. between these will be alternating also. The complete fixed armature, that is magnetic core and windings, is called the stator, and the rotating field system the rotor. The general constructional features of a salient pole alternator are shown below
shematic of salient pole generator
As the field system rotates and carries its flux with it, each portion of the stator core will experience reversals of magnetisation, and therefore, as in a direct current machine, the core has to be laminated. For ventilation purposes, a series of radial ventilating ducts are provided. Since the field system rotates, its exciting winding has to be fed by means of two slip rings, but as the excitation voltage is low and the power taken by the field winding small, these present no difficulties
A salient pole has one field coil per pole, very like a D.C. machine. For the very high speeds of turbine driven alternators it is necessary to adopt a cylindrical construction for the rotor and in such a case the field winding has to be housed in a number of slots. A simplified form shows the cross section of a four pole turbo alternator , the dispostion of the rotor field of a turbo alternator rotor may be as high as 40,000 ft per min or 200 metres per sec. The stresses due to centrifugal force are exceedingly high. The rotors are thus made from steel forging, or in some cases from thick steel discs bolted together.

high speed rotor

Schematic of high speed solid core rotor The axial length is normally considerably greater than the diameter. Has the advantage of great strength and stiffness. The exciting current is carried by bar type conductors in the groups of slots shown below. All currents in one group are in the same direction , those on the next group on the opposite direction. Flux produced is distributed over surface approximately according to sine law.

Details of stationary armature alternators.

Stamping making up stator Armature stampings pressed out of sheets of special magnetic iron or steel alloy. In the smaller sizes the stampings are pressed out in compete rings
Section through top stator of salient pole machine.
Section through top stator of salient pole machine. The armature core is built up of laminations which are held tightly together by end clamping rings. Spacing strips inserted at intervals leave ducts for cooling air to pass through. The air is driven through by the fan action of the rotor and escapes via the apertures in the cast iron supporting frame.
Different types of slots found in a stator.
Types of armature slot. The filled slot has round wires but it is common to have rectangular conductors to economise slot space.
Layout of conductor slot showing conductors bounded by tpae in a micantite insulator.

Sectional simplified diagram of a turbo alternator

The rotor is turned from a steel forging ans slotted to carry the exciting windings the slots being arranged as shown above. Because of the high running speed, alternators for large outputs have a considerable axial length compared with rotor diameter. Modern generator layout.

Layouts of A.C. generators


Conventional excitation scheme (Rotary)

Separately excited D.C. exciter (Out dated) Seperately excited

Brushless excitation scheme using shaft mounted diodes (Rotary)

Indirect self excitation (Error) indirect self excited
Comparison of the value required to control with a fixed value. When the variable differs from a fixed reference value an 'error' exists and the function of the controlling medium is to restore equilibrium e.g. if the voltage output falls on the brushless rotary excited alternator the a.v.r. controls the exciter field to restore equilibrium.

Modern compound scheme (static)

Direct self excited (Functional) direct self excited
Control of the voltage to a set value is achieved by the inherent characteristics of the machine.
A compound wound d.c. generator with a level compound characteristic has additional current in the series field under load conditions. In the self excited compound alternator there is a constant amount of excitation required for no load condition. Additional excitation due to more current form the current transformers is obtained in response to extra external demands

Recovery graphs for 'functional' and 'error' layouts

graph of voltage recovery

Shaft driven generating system


    Methods of drive
    1. Belt or chain driven
    2. Direct coupling engaging the propeller shaft
    3. Power taken from the main gearbox.
    4. Power taken from the free end of the engine
With D.C. auxiliaries power can be taken by either a chain or belt drive from the propulsion system with an A.V.R. maintaining constant voltage.
For A.C. systems methods used include the use of a D.C. generator with an D.C./A.C. converter, or direct A.C. generation. With the latter either a constant speed drive is required or a frequency converter. With either method the revolutions at which the shaft alternator can be used is limited. In this way direct drive systems will generally be fitted in conjunction with a C.P. system which maintains constant engine speed under full away conditions.

    Advantages
    1. Saving on fuel costs, allows efficient use of heavy rather than gas oil
    2. reduced maintenance costs
    3. Capital saving on reduced number of auxiliary sets
    4. Reduced space and weight
    5. Reduction in noise

    Disadvantages
    1. Power available for propulsion reduced
    2. Capitol cost of plant
    3. Auxiliaries required for manoeuvring, although some medium speed plants are capable of manoeuvring with shaft alternators and C.P. system
    4. Complicated constant speed or frequency gear required with slow speed engines